Software User Manual FRN 1.2 Owner manual
Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 287
Command Number 6: Read the Disable/Enable Flow Calculation
Setting
Use command number 6 to read the disable/enable setting of the flow
calculation for a meter run.
There is no event code for command number 6.
Event codes for command number 5
Event Name Event Code
EVENT_RUN_ENABLE 11
EVENT_RUN_DISABLE 12
Return codes for command number 5
Return Code Description
00 OK
01 Meter run is invalid
02 Input value is invalid
100 Pass code is incorrect
Other Invalid
Parameters for command number 6
Address Data Type Attribute Description
49025 u_short RW 6
49026 u_short R Return code
49027 u_short W Meter run (0…7)
49028 u_int W Pass code for user
49030…49034 — — Reserved
49035 u_short R 0: Disable
1: Enable
Return codes for command number 6
Return Code Description
00 OK
01 Meter run is invalid
100 Pass code is wrong
Other Invalid