Software User Manual FRN 1.2 Owner manual

Publication 1758-UM002D-EN-P - October 2010
Extension Modbus Protocol for DataSite Controllers (1758-FLO) 273
Modbus addresses for calculation results block 2
Meter Run Starting Address Parameter
Address
Address Number
0 33101 X 50
1 33151 X + 50 50
2 33201 X + 100 50
3 33251 X + 150 50
4 33301 X + 200 50
5 33351 X + 250 50
6 33401 X + 300 50
7 33451 X + 350 50
Parameters in calculation results block 2
Parameter Name Description Data Type Modbus Addresses
for Meter Run 0
Parameters (= X)
qeh_pval Energy hour flow rate float 33101…33102
qe_yesterday Energy flow of the previous day float 33103…33104
avh_EXT Hourly average of the square root of the product of static pressure and
differential pressure. This is also the average uncorrected volume
(AGA7) for the hour.
float 33105…33106
avd_EXT Daily average of the square root of the product of static pressure and
differential pressure. This is also the average uncorrected volume
(AGA7) for the day.
float 33107…33108
avh_Gr Average real relative density for the hour float 33109…33110
avd_Gr Average real relative density for the day float 33111…33112
Y2 Expansion fsactor based on the absolute static pressure measured at
the downstream tap
float 33113…33114
Reserved Reserved float 33115…33150