Software User Manual FRN 1.2 Owner manual

Publication 1758-UM002D-EN-P - October 2010
216 DataSite Flow Configuration Utility (DS FloConfig)
HART state register +0 = state 0
+1 = state 1
Command 35
Purpose Write Primary Variable Range Values
Send register +0 = Primary Variable 0 code, 8-bit unsigned integer
+1, 2 = Primary Variable upper range value (float point)
+3, 4 = Primary Variable lower range value (float point)
Return register Not used
Unit register Not used
HART state register +0 = state 0
+1 = state 1
Command 38
Purpose Reset Configuration Changed Flag
Send register Not used
Return register Not used
Unit register Not used
HART state register +0 = state 0
+1 = state 1
Command 40
Purpose Enter/Exit Fixed Primary Variable Current Mode
Send register +0, 1 = Actual fixed Primary Variable current level, units of
milliamperes (float point)
Return register Not used
Unit register Not used
HART state register +0 = state 0
+1 = state 1
Command 44
Purpose Write Primary Variable Units
Send register +0 = Primary Variable units code, 8-bit unsigned integer
Return register Not used
Unit register Not used
HART state register +0 = state 0
+1 = state 1
Command 48
Purpose Read Additional Transmitter Status
Send register Not used
Description of HART commands (Continued)