Software User Manual FRN 1.2 Owner manual

Publication 1758-UM002D-EN-P - October 2010
DataSite Flow Configuration Utility (DS FloConfig) 187
Test the Communication
Follow these steps to obtain the communication settings of the DataSite
controller. This function can help you retrieve the communication parameter
settings if you forget or lose them.
1. Set the controller into the Service mode.
2. Select the Communication Test check box.
3. Click Set.
All settings will be downloaded into the controller.
4. Click Run followed by Close.
The controller goes into the Communication Test mode. The
communication parameters of COM2 are set to be test parameters.
This table lists the communication test parameters.
COM2 communication test parameters
Parameter Name Parameter Value
Station 1
Protocol Modbus RTU
Master/Slave State Slave
Duplex Full
Baud rate (bps) 57600
Parity None
Data bits 8 bits
Stop bits 1 bit
Port type RS232
Timeout (10 ms) 100
Delay time (10 ms) 0