Software User Manual FRN 1.2 Owner manual
Publication 1758-UM002D-EN-P - October 2010
DataSite Flow Configuration Utility (DS FloConfig) 143
Configure Field Signal Parameters for the AGA7 Standard
If you have chosen the AGA7 standard, you need to configure the parameters
for the field signals accordingly.
For information on how to set the parameters for the pressure and
temperature signals, see Configure Field Signal Parameters for the AGA3
Standard on page 140.
The pulse address is the address of the pulse signal from the PI (Pulse In)
channel. You can choose from the PI 0…PI2 channels on the DataSite
controller. The variable, k, is the k factor of turbine (pulses per cubic feet).
TIP
For any changes to parameter settings to be applied to the
DataSite controller, you need to click Download.
IMPORTANT
Before downloading any changes to the DataSite controller,
it is recommended that you perform an upload. This helps
prevent modifying information that you did not intend to
change.
Input Address Data Type Data k
PI0 30011 USHORT PI0 count value k factor of turbine
PI1 30013 USHORT PI0 count value k factor of turbine
PI2 30015 USHORT PI0 count value k factor of turbine
User defined
signal source
Address in
4xxxx
USHORT Simulation data
input which is
always increasing
User defined k