Installation Instructions Owner's manual

DataSite Natural Gas Flow Meter and Remote Terminal Unit 23
Publication 1758-IN001C-EN-P - June 2011
Voltage input impedance 100 k for 10V DC inputs
170 for 20 mA inputs
Input Resolution 16-bit
Non-linearity ±0.1% of full scale
Overall accuracy ±0.1% of full scale at 25 °C
±0.3% of full scale over temperature range
Voltage Input Overvoltage
Protection
Continuous input must not exceed 160% of the rated range
Analog Outputs
Attribute Description
D/A resolution ratio 16-bit
Power supply Successive approximation
Output signal range 4…20 mA
Maximum load
Impedance
1000 with 24V DC loop power
400 with 12V DC loop power
Output type Single ended regulation on positive side with common negative return
Isolation voltage 70V AC or 100V DC
Absolute accuracy ±0.2% (25 °C with 250 load)
±0.5% (full temperature range, 0…1000 load)
Response time 100 ms typical (10…90%)
Noise and ripple, max 0.04%
Transient protection 600 W
HART
Attribute Description
Modulation Frequency Shift Keying (FSK)
Logic 1 - 1200 Hz
Logic 0 - 2200 Hz
Data rate 1200 bps
Transmit level 500 mVp-p / 250
Receive sensitivity 120 mVp-p/ on
80 mVp-p/ off
Analog Inputs
Attribute Description