Publication IASIMP-QS008A-EN-P - March 2009 69
System Validation Chapter 6
Validate DataSite to PanelView Plus Communication
You are now ready to validate communication between the DataSite unit and the PanelView Plus
terminal. Using the DS FloConfig software, you will simulate three process variables and validate
that the calculated flow values display on the PanelView Plus terminal.
Follow these steps to perform the system validation.
1. Launch the DS
FloConfig software.
The path shown may
be different on your
computer depending
on where the
software is installed.
2. Select Open Recent
Project and click OK.
This DS FloConfig file was created in Chapter 1.
TIP
To use actual process variables, wire temperature, pressure, and differential pressure transmitters to the
DataSite analog inputs.