Installation and Upgrade Guide
Publication 1757-IN510A-EN-P - October 2003
Operating System Installation Procedures 2-15
8. Verify the information on the Regional Settings window and
click Ne x t .
9. Enter the appropriate Name and Organization name and click
Ne x t .
10. Enter your Windows 2000 Professional Product Key and click
Ne x t .
11. At the Computer Name and Administrator Password window:
a. Enter the Computer Name.
b. Enter the Administrator password.
c. Confirm the password.
d. Click Ne x t .
12. At the Date and Time Settings window:
a. If necessary, adjust the Date and Time settings.
b. Set the appropriate Time Zone for your location.
c. Uncheck the Automatically adjust clock for daylight saving
changes option.
d. Click Ne x t .
13. If setup has not found a suitable Network Device, you are
prompted to install one. Follow the instructions for adding a
manufacturer supplied driver or add the Microsoft Loop Back
adapter.
IMPORTANT
The computer name cannot contain more than 14
alphanumeric characters and must contain no spaces.
For a ProcessLogix Client, be sure the name does not
end in the letter “A” or “B”. The suggested name is
STNxx, where xx is the Station Number (01-20).
IMPORTANT
Be sure to document the Administrator password, it
is required later in the procedure. The Administrator
account and password gives a user full access to the
system. Care should be taken to who has access to
this information.
ATTENTION
!
Failure to uncheck the Automatic adjustment for
Daylight Savings Time causes Redundant Systems to
lose “Sync” when the time is automatically adjusted.
Choosing not to automatically adjust the time
allows you to decide when to make the adjustment
(at a time that is not critical to your process).