Installation and Upgrade Guide

Publication 1757-IN510A-EN-P - October 2003
Supplementary Procedures 8-25
procedure to confirm that any client reference the correct
non-redundant server or computer name or IP address.
Setting up a ProcessLogix Client with Redundant Servers
If ProcessLogix Client is networked to redundant Servers, refer
to ProcessLogix Client Supported Installations on page 1-4.
Adding 1757-PLX52
Controller Redundancy to
R510.0 Non-Redundant
1757-PLX52 Controller
Configurations
Deleting a Non-Redundant 1757-PLX52 and Unassigning its
Contents
Complete the following steps to save your existing database and
delete it from the existing non-redundant 1757-PLX52 Controller.
1. Start Control Builder.
2. Close any open Control Module and/or Sequential Control
Module.
3. In Monitoring tab, expand the non-redundant CPM to display
the CEE folder icon.
4. Click the CEE folder icon.
5. Click Tools Upload with Contents to upload the existing
controller database.
6. Click Con tin ue.
This may take considerable time to complete, depending on the
amount of CM/SCMs (and their number of FBs and/or number
of Steps/Transitions) currently assigned to this CEE.
7. Click the CEE folder icon.
8. Click Tools Update with Contents (to Project) to save the
existing controller database.
ATTENTION
!
Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.