Installation and Upgrade Guide
Publication 1757-IN510A-EN-P - October 2003
4-24 ProcessLogix Server Upgrade Procedures
Exporting the R320.0 Engineering Repository Database
Stopping the ER Replicator Service
This procedure is required for a Redundant Server pair only. Complete
these steps on SERVERB only. If you have a non-redundant server,
skip to Exporting the Database Using Control Builder on page 4-24.
1. Logon to SERVERB as plx_user.
2. Click Star t ⇒ Settings ⇒ Control Panel.
3. Double-click Services.
4. Select the PlantScape ER Replicator service and click Stop.
5. Click Yes to confirm.
6. Close the Services and Control Panel windows.
Exporting the Database Using Control Builder
Complete these steps on a non-redundant Server or SERVERB.
1. Using Windows Explorer, create the folder C:\Data\ExportDB.
2. Click Star t ⇒ Pr ogr ams ⇒ ProcessLogix Engineering Tools
⇒ Con tr ol Builder.
3. In the Login dialog box, make these entries:
IMPORTANT
You must export the Engineering Repository
Database at this time before proceeding.
To save the CM block parameter values to the
Monitor image, it is recommended to do the
following:
1 . Upload with Contents of your Control Modules.
2. Update to Project, which saves the Monitor
image to the Project image.
This procedure captures the latest configuration
changes. Otherwise, after re-loading the CMs
following the Processlogix upgrade, changed values
would be lost.