Installation and Upgrade Guide Instruction Manual

Publication 1757-IN500A-EN-P - September 2002
ProcessLogix Server Upgrade Procedures 4-7
Station setup file Document any changes that were made to the default
Station setup file.
The new default setup file is configured to as
“static
Station 1”. If this is not correct, you must
make the appropriate changes via Station’s Setup
menu.
Navigate in Knowledge Builder to Server and
Client Configuration Guide
Configuring Stations
and Printers
Setting Up Station for more
information.
Log file If desired, create a backup copy of the log file found in
C:\Honeywell\server\data\.
The log file has been renamed to log.txt.
History archive
search path
Document the history archive search path. After upgrading, you must specify the history
archive search path using the ProcessLogix Server
Control Panel.
Navigate in Knowledge Builder to Server and
Client Configuration Guide
Understanding and
Configuring Points
History Collection and
Archiving
History Archiving for more
information.
Custom applications Backup any custom applications built for your existing
system.
Custom applications must be re-compiled and
re-linked using an appropriate development
environment.
Navigate in Knowledge Builder to Application
Development Guide
About the Development
Environment
Compiling, Linking, and Editing for
more information.
Quick Builder
projects
Backup any Quick Builder projects. When opening an old project file with the new
version of Quick Builder, you are prompted to
migrate the project file to the new format.
File dumps Do not use any file dumps of the pre-upgrade
database to restore the upgraded database.
Hardware definition
files
If you want to use existing hardware definition (hdwbld)
files to build printers, you must change the CYRILLIC
keyword to LANGUAGE=CYRILLIC.
Alarms and
messages
Resolve any alarms before starting the upgrade. Alarms
and messages currently in the system cannot be copied
across for the upgrade.
Handover notes Handover notes are lost during the upgrade. Handover
notes in the system cannot be copied for the upgrade.
Table 4.D Upgrading an R320.0 Server Considerations
Item Pre-upgrade Requirement Post-upgrade