Installation and Upgrade Guide Instruction Manual

Publication 1757-IN500A-EN-P - September 2002
7-16 Firmware Maintenance Procedures
3. Enter this command:
>ntools -c -pg<
4. Click OK to launch the Network Tools application.
5. Click OK to acknowledge the warning about monitoring through
Control Builder.
6. Click Resume to initiate network scan.
7. Click any CNB icon under the Desktop tree and wait for the graphic of
the chassis to appear in the Detail pane.
8. In the graphic of your chassis, click the CNB module with the Network
Address selected above.
9. Click Change ControlNet to call up the Keeper Values dialog box.
10. Confirm that the values listed for the parameters under the Changes Tab
on the dialog box match the following settings and key in new values, as
required.
TIP
If the RSLinx and PCIC driver services for system
communications in ControlNet mode are not running,
this command will start the services.
TIP
This may be the only module that appears in the
chassis graphic at this time.