Installation and Upgrade Guide User guide
Publication 1757-IN032B-EN-P - April 2001
System Software Upgrade Procedures 1-71
Synchronizing Server Databases on Redundant Servers
31. Click Start⇒Programs⇒ProcessLogix Server⇒Station.
32. Click View
⇒System Status⇒Server Redundancy to call up the
Server redundancy display.
33. Click the Oper field in the lower right corner of the display.
34. Key in >mngr< in the open Enter password field above the
display and press <Enter>.
35. Click Synchronize. When the Synchronize Databases (Y/N)
prompt appears, key in >Y< in the entry field above the display
and press <Enter>.
36. Wait for the synchronization to complete (“Synchronization
Complete” prompt appears) and verify that the display shows
simulated Green LED indications for the following states:
Primary Server
• Running
Backup Server
• Synchronized
• Running
Link Status
• Link 0 (LNK00) - In use for control & data information
37. Click Station
⇒Exit.
38. Click OK to exit Station.