Installation and Upgrade Guide User guide

Publication 1757-IN032B-EN-P - April 2001
1-40 System Software Upgrade Procedures
Reconfiguring Other RSLinx Clients
Other applications which utilized the deleted 9904-KTCX15 driver must
be reconfigured for the 1784-PCIC driver.
Reloading the 1757-PLX52 Database
Use the following procedure to log on and check Control Builder
operation after the R320.0 software is installed.
1. Click Start
ProgramsProcessLogix Engineering
Tools
Control Builder.
2. In the Login dialog box, make these entries:
a. Key in >mngr< as the default User Name.
b. Key in >mngr1< as the default Password.
c. Key in >localhost< in the Server Name field.
3. Click OK.
4. In the Project tab, confirm that the components of your configured
control strategy are listed in the Root directory.
If using: You must:
NI-FBUS
reconfigure the NI-FBUS communications software to use
the new 1784-PCIC card
navigate in Knowledge Builder to Linking
Device Implementation Guide
Installation
Configure the NI-FBUS Interface for more
information
use AB_PCIC-1 for the Driver name
SCADA points
reconfigure the Channel for the 1784-PCIC
navigate in Knowledge Builder to
Controller References
Allen-Bradley Controller Reference
Defining a
Allen-Bradley Channel
for more information.
use AB_PCIC-1 for the Driver name
ATTENTION
!
If you also upgraded from a non-redundant
1757-PLX52 to a redundant 1757-PLX52, you must
delete the existing CPM and its associated CEE from
the Project tab, reconfigure a new 1757-PLX52 and its
associated CEE, and reassign the components before
you download the CPM to the Controller.