Installation and Upgrade Guide User guide

Publication 1757-IN032B-EN-P - April 2001
1-32 System Software Upgrade Procedures
a. Select the Service and click Startup.
b. In the Startup Type field, click the Manual option and click OK.
The following Services should be changed to Manual Startup:
ProcessLogix ER Replicator (redundant SERVERB node only)
ProcessLogix ER Server
ProcessLogix System Repository
ProcessLogix Control Data Access Server
ProcessLogix Server Daemon
ProcessLogix Server Database
ProcessLogix Server System
5. Click Start
Shut Down and select the shutdown the computer
option.
6. Power down the PC.
Continue with the updating of the 1784-PCIC card firmware.
1. Turn on the PC and logon as plx_user.
2. Click Start
Run.
3. Key in this command in the Open entry field:
>C:\Honeywell\TPS50\System\Firmware\1784-PCIC\3_3\Setup.exe.<
4. Click OK.
5. At the Welcome to ControlFLASH Setup window, click Next.
6. Click Next to accept the default location.
7. Uncheck the Yes, I want to view the ControlFLASH readme file.
8. Check Yes, I want to launch ControlFLASH and click Finish.
9. At the Welcome to ControlFLASH window, click Next.
10. Click 1784-PCIC and click Next.
11. Double-click on AB_PCIC1.
12. Confirm that the update revision is 3.3 and click Next.
13. At the Summary window, click Finish.