Installation and Upgrade Guide User guide

Publication 1757-IN032B-EN-P - April 2001
Performance and Capacity Specifications 7-17
1757-PLX52 Resources
Table 7.U 1757-PLX52 Configuration Options
1757-PLX52 Configuration Options
1757-PLX52 Module Slot Width 2 slots
Base Execution Periods Supported
(different personalities required)
50 ms, 5 ms*
Note:
5 ms CEE not supported on
BETA-PLX52
50 ms CEE 5 ms CEE
Controller Redundancy Supported Yes No
Remote I/O Supported Yes No
I/O Module Execution Period 50 ms 5 ms
Configurable Values for CM/SCM Execution Periods 50, 100, 200, 500,
1000, 2000 ms
5, 10, 20, 50, 100,
200 ms
Configurable Values of Peer Update Rates (period).
Defines the period at which data is updated for all
‘pull/get’ requests for peer data required by all
blocks within a CEE.
*Supervisory Ethernet LAN systems only guarantee a
Pull/Get Request Rate of 500 msec or greater. Faster
Pull/Get rates can be configured, however, data arrival
at the configured rate cannot be guaranteed for rates
faster than 500 msec.
100, 200, 500*,
1000* ms
10, 20, 50, 100,
200, 500*, 1000*
ms
Table 7.V 1757-PLX52 Processing Resources
1757-PLX52 Processing Resources
Definitions
:
PU = Processing Unit. The PU represents a platform independent amount of processing resources
(time) required to complete a predefined amount of computational (control) work.
Maximum Cycle Loading: Over an cycle (0-39), the “Average CPU Used” (CPUCYCLEAVG) statistic
is not to exceed the stated maximums.
Minimum Reserved CPU to be Maintained During
Runtime (CPUFREEAVG)
20%
1757-PLX52 Configuration PU Maximum Maximum Cycle
Loading
50 ms CEE – Non-Redundant Configuration 3600 PU/sec 60%
50 ms CEE – Redundant Configuration 1600 PU/sec 60%
5 ms CEE – (Non-Redundant only) 2400 PU/sec 40%