Installation and Upgrade Guide User guide
Publication 1757-IN032B-EN-P - April 2001
5-26 Supplementary Procedures
• Refer to Control Hardware Installation Guide ⇒Redundancy Module
Installation and Removal.
• Refer to Control Hardware Installation Guide
⇒Communication
Module Installation and Removal.
Checking firmware revision levels
Refer to Upgrading Hardware Component Firmware on page 2-1 to
check/upgrade 1757-PLX52, 1756-CNB, and 1757-SRM firmware.
Creating a Redundant 1757-PLX52
1. Refer to the Control Building Guide⇒Hardware Module
Creation
⇒Creating a Redundant PLX52 controller topic for more
information about configuring a redundant PLX52 in Control
Builder.
2. Once the redundant CPM is created in the Project tab, re-assign the
modules unassigned from the previous non-redundant CPM to the
CEE associated with the new redundant CPM.
3. Load the primary and secondary CPMs and RMs to the
Controllers.
This completes the upgrade to a Redundant Chassis Pair.