Installation and Upgrade Guide User guide
Publication 1757-IN032B-EN-P - April 2001
Full PC Software Installation Procedures 3-29
When the update is completed, ControlFLASH will report that the
1784-PCIC card failed to report the new revision number. Since the
3.3 firmware requires a different driver than the 1.4 card,
ControlFLASH does not reset the card when the update is
completed. This allows the card to continue functioning as a 1.4
card.
16. Click OK, and then click Cancel at the Welcome to
ControlFLASH Setup window.
17. Click Yes to end the configuration session.
18. Click Start
⇒Programs⇒Rockwell Software⇒RSLinx⇒RSLinx
to call up the Rockwell Software RSLinx window.
19. Click Communications
⇒Configure Drivers to call up the
Configure Drivers dialog box.
20. Click AB_PCIC-1 selection in the Configured Drivers list and click
Delete.
21. Click Close to close the Configure Drivers dialog box.
22. Close RSLinx.
23. Click Start
⇒Settings⇒Control Panel.
24. Double-click the Services icon.
25. Change ALL the ProcessLogix Services Startup Type to Automatic.
To change a Service Startup Type to Automatic:
a. Select the Service and click Startup.
b. In the Startup Type field, click the Automatic option and click
OK.
The following Services should be changed to Automatic Startup:
• ProcessLogix ER Replicator (redundant SERVERB node only)
• ProcessLogix ER Server
• ProcessLogix System Repository
• ProcessLogix Control Data Access Server
• ProcessLogix Server Daemon
• ProcessLogix Server Database
• ProcessLogix Server System