Installation and Upgrade Guide User guide
Publication 1757-IN032B-EN-P - April 2001
Firmware Maintenance Procedures 2-17
4. Click OK to launch the Network Tools application.
5. Click OK to acknowledge the warning about monitoring through
Control Builder.
6. Click Resume to initiate network scan.
7. Click any CNB icon under the Desktop tree and wait for the
graphic of the chassis to appear in the Detail pane.
8. In the graphic of your chassis, click the CNB module with the
Network Address selected above.
9. Click Change ControlNet to call up the Keeper Values dialog
box.
10. Confirm that the values listed for the parameters under the
Changes Tab on the dialog box match the following settings and
key in new values, as required.
TIP
This may be the only module that appears in
the chassis graphic at this time.