Software User Manual Owner's manual
Publication 1757-UM002B-EN-P - January 2003
5-6 Import/Export
TagMap Declarations
An unlimited number of TagMaps can be defined in each Group. Each
TagMap is declared with a
TAGMAP statement. The fields in a TAGMAP
declaration are in Table 5.C.
Table 5.C TagMap Declarations
Field # FIELD NAME FIELD TYPE FIELD DESCRIPTION Examples
1 Line Type String Contains the string TAGMAP to define this line in the CSV
file as a TagMap.
TAGMAP
2 Description String Specifies the description of this TagMap. This field cannot
contain any commas. May be left blank.
User specified.
3 ProcessLogix
OPC Item name
String Specifies the OPC Item name to connect with in
ProcessLogix.
YHS103_B.DEVCTL
A.MODE
4 ProcessLogix
Access Path
String Specifies the ProcessLogix OPC Access Path to connect
with. May be left blank.
5Ext. Server
OPC Item Name
String Specifies the OPC Item name to connect with in the
External Server.
Device1.TIC108_B.
MODE
6Ext. Server
Access Path
String Specifies the Access Path to connect with in the External
Server. May be left blank.
7 Translation Table
Name
String Specifies the Translation Table name used for scaling by
this TagMap. May be left blank if no scaling is required.
Device Output
8 Data Master Integer Specifies which server is the Data master if the Group’s
Data direction is set to bi-directional. Note, this setting is
overwritten by the Groups data flow direction if not
bi-direction.
0-ProcessLinx
1-External Server
0 or 1
9 Use Mode Attribute
flag
Integer Specifies that the TagMap will use the Mode Attribute OPC
Item for sending data to ProcessLogix.
1-True, 0-False
0 or 1