Installation Instructions ProcessLogix Fieldbus Interface Module (FIM) (Catalog Number 1757-FIM) For information about: See Page: Important User Information 2 Planning Considerations 4 Installing Fieldbus Interface Module 1757-FIM 5 Loading 1757-FIM Firmware 6 Hazardous Locations 7 Specifications 8 Package Contents: • 1 Fieldbus Interface Module (1757-FIM) • installation instructions Publication 1757-IN913A-EN-P - October 2001
ProcessLogix Fieldbus Interface Module (FIM) Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
ProcessLogix Fieldbus Interface Module (FIM) ATTENTION ! 3 Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
ProcessLogix Fieldbus Interface Module (FIM) Planning Considerations Fieldbus Network References Refer to the following publications for guidance in designing and implementing the Fieldbus network to be interfaced to the ProcessLogix system through the FIM and its companion Remote Termination Panel (RTP). Pub Number Publication Title Scope Source AG-140 Wiring and Installation 31.
ProcessLogix Fieldbus Interface Module (FIM) 5 Installing Fieldbus Interface Module 1757-FIM Inserting the Module Use the following steps to insert the FIM into the chassis: ATTENTION ! Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • • • • • • Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap.
ProcessLogix Fieldbus Interface Module (FIM) 3. Align the sides of the module with the chassis guides. chassis guides 4. Slide the module into the chassis until the module tabs snap into position. Loading 1757-FIM Firmware ATTENTION ! If the FIM is not installed and pre-configured by the factory, users must load the FIM’s firmware to make it fully operational. This is also true for any replacement FIM ordered separately from the factory.
ProcessLogix Fieldbus Interface Module (FIM) 7 Hazardous Locations The following information applies when Informations sur l’utilisation de cet équipement en operating this equipment in hazardous locations: environnements dangereux : Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
ProcessLogix Fieldbus Interface Module (FIM) Specifications FIM Specifications Physical Interface H1 FOUNDATION Fieldbus Number of H1 Networks per FIM 1 (Each network defined as a FOUNDATION Fieldbus 31.25 kbps H1 network) 2 Maximum Number of Fieldbus Devices per H1 Network 30 2 Maximum Number of FIMs per 1757-PLX52 Controller (Each FIM counts as 3 IOMs in the IOMs/CPM calculation.
ProcessLogix Fieldbus Interface Module (FIM) 9 FIM Specifications Enclosure Type Rating None (open-style) Barometric Pressure Altitude -300 to +3000 m Certifications: (when product is marked) UL CSA FM CE 4 C-Tick4 UL Listed Industrial Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations European Union 89/336/EEC EMC Directive, compliant with: EN 5008
ProcessLogix Fieldbus Interface Module (FIM) Notes: Publication 1757-IN913A-EN-P - October 2001
ProcessLogix Fieldbus Interface Module (FIM) 11 Notes: Publication 1757-IN913A-EN-P - October 2001
Allen-Bradley and ProcessLogix are Trademarks of Rockwell Automation. Foundation Fieldbus is a trademark of the Fieldbus Foundation. Publication 1757-IN913A-EN-P - October 2001 PN 957536-50 © 2001 Rockwell Automation. All rights reserved. Printed in the U.S.A.