Rockwell Automation Publication 1757-UM012A-EN-P - July 2011 151
Troubleshoot the Linking Device Appendix A
2. Press the reset button.
Reset through RSFieldbus Software
By using RSFieldbus software, you can reset the linking device through the
Restart parameter in the Resource block.
1. While online in RSFieldbus software, right-click the Resource block of the
linking device and choose Online Characterization.
2. Select the Restart parameter and click Edit.
3. On the pull-down menu, choose the type of reset identified in the table.
ATTENTION: You will lose the following linking device functions during
a reset:
• Control of the current linking device process
• Monitoring processes through the linking device
• Communication to devices attached to the linking device
Value Reset Type Description
1 Run Run appears while the linking device is operating
normally. It returns to this value after a reset value
(default or factory) is transmitted
and completed.
2 Resource Not supported (do not select).
3 Defaults This resets all block parameters to default. All
blocks in the linking device are retained, including
tag names, and macrocycle times.
4 Processor Not supported (do not select).
5 Factory This deletes all blocks in the linking device except
for the Resource block. All Resource block
parameters are reset to factory default, including
the tag name.
43481-C
Reset Configuration Jumper
Factory-default Reset Button
(inside top cover)