Manual
80 Publication 1757-UM007D-EN-P - December 2008
Chapter 7 Monitoring the 1757-ABRIO Module
Refer to the following table for block transfer write diagnostics.
Monitoring the Scanner Log
The scanner log displays messages from the 1757-ABRIO firmware,
showing its normal operation and error messages. It may be useful in
tracking down errors and for Technical Support.
To monitor the scanner log, select Tools>Monitor Scanner Log.
To clear the scanner log, select Edit>ClearLog or click the Clear Log
button.
To copy the contents of the log to the Windows clipboard for use in
another application, select Edit>Copy or click Select All then the Copy
button.
Ignored Req Running count of update requests ignored by the block
transfer module.
Prot Errors Running count of protocol errors for this block transfer read.
If this counter is incrementing, the module isn't responding
correctly. Possible causes are length mismatch, invalid reply.
Request Count Count of the number of times on successive scans this block
transfer was requested. If this is consistently a high number,
increase the requested update time - the module cannot
respond quickly enough at the current requested time. The
counter applies to both the BTR and BTW for this module.
Block Transfer Write Diagnostic Data
Counter Description
CFG len Length of the configuration data for this module.
BTW data len data length
Req Update Time Requested update time in module configuration, in ms.
Avg Update Time Average update time for this block transfer write, in ms. This
is the average of the previous 8 updates.
Min Update Time Minimum update time for this block transfer write, in ms.
Max Update Time Maximum update time for this block transfer write, in ms.
Update Count Running count of updates for this block transfer write.
Ignored Req Running count of update requests ignored by the destination
module for this block transfer write.
Prot Errs Running count of protocol errors for this block transfer write.
Block Transfer Read Diagnostics
Counter Description