Manual

Publication 1757-UM007D-EN-P - December 2008 151
Tag Descriptions for Scheduled Data in RSLogix 5000 Software Appendix C
Status Tag
The status tag contains a global status as well as individual status flags
for all possible partial racks. The status bits are set if the rack with the
corresponding rack number and starting I/O group is configured in
the 1757-ABRIO module and is not communicating, and are 0
otherwise. If any configured rack is not communicating, the global
status is set.
The following table shows the contents of the Status Tag.
Status Tag
Address Description
Local:<slot>:S.Data[0] Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.
Local:<slot>:S.Data[1] Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.
Local:<slot>:S.Data[2].0 Not used
Local:<slot>:S.Data[2].1 Not used
Local:<slot>:S.Data[2].2 Not used
Local:<slot>:S.Data[2].3 Not used
Local:<slot>:S.Data[2].4 Rack 1, I/O group 0 error
Local:<slot>:S.Data[2].5 Rack 1, I/O group 2 error
Local:<slot>:S.Data[2].6 Rack 1, I/O group 4 error
Local:<slot>:S.Data[2].7 Rack 1, I/O group 6 error
Local:<slot>:S.Data[2].8 Rack 2, I/O group 0 error
Local:<slot>:S.Data[2].9 Rack 2, I/O group 2 error
Local:<slot>:S.Data[2].10 Rack 2, I/O group 4 error
Local:<slot>:S.Data[2].11 Rack 2, I/O group 6 error
Local:<slot>:S.Data[2].12 Rack 3, I/O group 0 error
Local:<slot>:S.Data[2].13 Rack 3, I/O group 2 error
Local:<slot>:S.Data[2].14 Rack 3, I/O group 4 error
Local:<slot>:S.Data[2].15 Rack 3, I/O group 6 error
Local:<slot>:S.Data[3].0 Rack 4, I/O group 0 error
Local:<slot>:S.Data[3].1 Rack 4, I/O group 2 error
Local:<slot>:S.Data[3].2 Rack 4, I/O group 4 error
Local:<slot>:S.Data[3].3 Rack 4, I/O group 6 error
Local:<slot>:S.Data[3].4 Rack 5, I/O group 0 error
Local:<slot>:S.Data[3].5 Rack 5, I/O group 2 error
Local:<slot>:S.Data[3].6 Rack 5, I/O group 4 error
Local:<slot>:S.Data[3].7 Rack 5, I/O group 6 error