Owner's manual

78 Rockwell Automation Publication 1756-UM058G-EN-P - November 2012
Chapter 4 Diagnostic Module Features
Pulse Test
Pulse test is a feature found on diagnostic output modules that can verify output-
circuit functionality without actually changing the state of the output load
device. A short pulse is sent to the targeted output circuit. The circuit should
respond as it would if a real change-of-state command was issued, but the load
device does not transition.
See page 227
in Appendix C for instructions on performing a pulse test with a
CIP Generic Message instruction.
The table explains how a pulse test can be used to perform a preemptive diagnosis
of possible future module conditions.
TIP
Consider the following when using the pulse test:
Only use the test when the output state does not transition for long periods
of time. Normal diagnostics will catch faults if the outputs are transitioning
regularly.
When first performing the pulse test, verify that the load will not
transition. You should be at the actual load while the test is performed.
Objective Pulse Test Description
Detect a blown fuse before it
happens
The Blown Fuse diagnostic can be used only when an output module is in the On
state. However, you can use a pulse test when an output module is in an Off state to
determine whether operating conditions may cause a blown fuse.
When you perform a pulse test on a module in the Off state, the output point is
commanded to be On briefly. Although no diagnostic bits are set in the output data
echo, the pulse test reports a failure if the conditions when the point is On indicate a
blown fuse may occur. See Point-level Fault Reporting on page 70.
IMPORTANT
The pulse test does not guarantee a fuse will blow
when the output point turns On. It merely indicates a
blown fuse is possible.
Detect a No Load condition
with an output On
No Load detection can only detect a fault when an output point is in the Off state.
However, you can use a pulse test when an output module is in an On state to
determine whether operating conditions for a point may cause a No Load condition.
If you perform a pulse test on an output point while it is in the On state, the output
point is commanded to be Off briefly. The pulse test reports a failure because
conditions when the point is Off indicate the possible absence of a field device; in this
case, though, the No Load bit will not be set. See Point-level Fault Reporting
on
page 70.
IMPORTANT
The Pulse Test does not guarantee the absence of a
load. It merely indicates a No Load condition is
possible.