Owner's manual

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012 187
Tag Definitions Appendix B
Table 38 - Standard Output Module Input Data Tags
Name Data Type Definition
CSTTimestamp
(8 bytes)
DINT[2] Coordinated System Time TimestampTimestamp of diagnostic input data including fusing (see BlownFuse,
NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.
Data
(1 bit per point)
DINT Data—Off/On status for the output point echoed back from the output module. This is used to verify proper
communication only. No field side verification is done. For field side verification, see OutputVerifyFault.
0 = Off
1 = On
Fault
(1 bit per point)
DINT FaultThis is an ordered status of faults that indicates a point is faulted and I/O data for that point may be incorrect.
Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input
module is lost, then all points for the module will be faulted.
0 = No fault
1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)
FuseBlown
(1 bit per point)
DINT Fuse Is BlownAn electronic or mechanical fuse has detected a short or overload condition for an output point. All
FuseBlown conditions are latched and must be reset by the user.
0 = No fault
1 = Fault
Table 39 - Standard Output Module Output Data Tags
Name Data Type Definition
CSTTimestamp
(8 bytes)
DINT[2] Coordinated System Time TimestampTimestamp to be used with scheduled outputs and coordinated system time
(CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module
is to apply its outputs.
Data
(1 bit per point)
DINT Output StatusOn/Off status of the output point originating from the controller.
0 = Off
1 = On
Table 40 - Diagnostic Output Module Configuration Tags
Name Data Type Definition
FaultLatchEn
(1bit per point)
DINT Latch Fault—If enabled for a point, any NoLoad, OutputVerifyFault or FieldPwrLoss stays latched in the faulted state
even if the fault no longer exists until the user clears the fault. This does not affect FuseBlown; it is always latched.
0 = Disable
1 = Enable latching
FaultMode
(1bit per point)
DINT Fault ModeUsed in conjunction with FaultValue to configure the state of outputs when a communication fault occurs.
See FaultValue.
0 = Use FaultValue (Off or On)
1 = Hold Last State
FaultValue
(1 bit per point)
DINT Fault ValueUsed in conjunction with FaultMode to configure the state of outputs when a communication fault occurs.
See FaultMode.
0 = Off
1 = On
FieldPwrLoss
(1 bit per point)
DINT Field Power Loss—Enables Field Power Loss diagnostic.
0 = Disable
1 = Enable
NoLoadEn
(1 bit per point)
DINT No Load—Enables No Load diagnostic.
0 = Disable
1 = Enable
OutputVerifyEn
(1 bit per point)
DINT Output Verify—Enables Output Verify diagnostic.
0 = Disable
1 = Enable