Owner's manual

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012 17
What Are ControlLogix Digital I/O Modules? Chapter 1
Module Identification and
Status Information
Each ControlLogix I/O module maintains specific identification information
that separates it from all other modules. This information assists you in tracking
all the components of your system.
For example, you can track module identification information to know which
modules are located in any ControlLogix chassis at any time. While retrieving
module identity, you can also retrieve module status.
Item Description
Product type Modules product type, such as digital I/O or analog I/O
Product code Modules catalog number
Major revision Module’s major revision number
Minor revision Modules minor revision number
Status Module’s status, including these items:
Controller ownership
Whether the module has been configured
Device-specific status, such as the following:
Self-test
Update in progress
Communications fault
Not owned (outputs in Program mode)
Internal fault (needs update)
Run mode
Program mode (outputs only)
Minor recoverable fault
Minor unrecoverable fault
Major recoverable fault
Major unrecoverable fault
Vendor Modules manufacturer vendor, such as Allen-Bradley
Serial number Modules serial number
Length of ASCII text string Number of characters in module’s text string
ASCII text string Modules ASCII text string description
IMPORTANT
You must perform a WHO service to retrieve this information. For more
information, refer to page 228
.