Chapter 11 Calibrate the ControlLogix Analog I/O Modules
The Output Reference Signals wizard appears to show which channels
will be calibrated for a high reference and the range of the calibration. It
also shows what reference signal is expected at the input.
14. Click Next.
15. Record the measurement.
16. Click Next.