Publication 1756-UM009C-EN-P - December 2010 269
Calibrate the ControlLogix Analog I/O Modules Chapter 11
10. Record the measurement.
11. Click Next.
A Results wizard displays the status of each channel after calibrating for
a low reference. If channels are OK, continue. If any channel reports an
error, retry steps
7
…
9
until the status is OK.
12. Click Next.
13. Set the channels to be calibrated for a high reference.