Publication 1756-UM009C-EN-P - December 2010 263
Calibrate the ControlLogix Analog I/O Modules Chapter 11
A Results wizard displays the status of each channel after calibrating for
a low reference. If channels are OK, continue. If any channel reports an
error, retry steps
7
9
until the status is OK.
11. Click Next.
12. Set the channels to be calibrated for a high reference.
The Output Reference Signals wizard appears to show which channels
will be calibrated for a high reference and the range of the calibration. It
also shows what reference signal is expected at the input.
13. Click Next.