Publication 1756-UM009C-EN-P - December 2010 223
Configure ControlLogix Analog I/O Modules Chapter 10
Limits Tab
The Limits tab lets you program clamping and ramp limitations that may
prevent damage to equipment.
1. Choose from the options on the Limits tab.
Field Name Description
Channel Click the channel that is being
configured.
Limits
High Clamp
Low Clamp
Type a high and low clamp value that
limits the output from the analog
module within this range.
See
page 152
and
page 170
for details.
See Important on
page 224
.
Ramp in Run Mode Check the box to enable ramping in Run
mode.
Ramp Rate Entry field is enabled if the Ramp in Run
Mode box is checked. Type a value that
sets the maximum ramp rate for a
module in Run mode.
See
page 169
in
Chapter 8
for details.
Disable All Alarms Check the box to disable all alarms.
Important: When you disable all
alarms, you disable process, rate, and
channel diagnostic alarms (for example,
underrange and overrange).
We recommend that you disable only
unused channels so extraneous alarm
bits are not set.