190 Publication 1756-UM009C-EN-P - December 2010
Chapter 9 Install ControlLogix I/O Modules
The table provides a quick reference to wiring guidelines for these analog
I/O modules.
Connect the Grounded End of the Cable
Before wiring the RTB, you must connect the ground wiring.
1. Do the following steps to ground the drain wire.
d. Remove a length of cable jacket from the Belden cable.
e. Pull the foil shield and bare drain wire from the insulated wire.
Cat. No. Page
1756-IF16 70
1756-IF8 74
1756-IF6CIS 106
1756-IF6I 109
1756-IR6I 138
1756-IT6I 139
1756-IT6I2 140
1756-OF4 157
1756-OF8 158
1756-OF6CI 177
1756-OF6VI 178
IMPORTANT
For all ControlLogix analog I/O modules except the 1756-IF6CIS
module, we recommend you ground the drain wire at the
field-side. If you cannot ground at the field-side, ground at an
earth ground on the chassis, as shown on
page 191
.
For the 1756-IF6CIS, we recommend you ground the module as
shown on
page 191
.