User Manual
ControlLogix Remote I/O (RIO) Module 17
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
Select the Proper Resistor
Use 82 resistors if the network operates at 230.4 kbps or if the network
operates at 57.6 kbps, or 115.2 kbps and none of the devices in this table are
present. The maximum number of devices on the network is 32.
Use 150 resistors if the network contains any of the devices in this table, or if
the network operates at 57.6 kbps or 115.2 kbps and you do not require the
network to support more than 16 devices.
Device Resistors
Cat. No. Series
1747-ASB All
1771-AS All
1771-ASB Series A
1775-S5 All
1794-ASB All
1771-DCM All
1771-SN All
1772-SD All
1772-SD2 All
1775-S4A All
1775-S4B All
1775-SR5 All
Baud Rate Cable Limits
Baud Rate Maximum Cable Length
57.6 Kbaud 3048 m (10000 ft)
115.2 Kbaud 1524 m (5000 ft)
230.4 Kbaud 762 m (2500 ft)