ControlLogix Isolated Analog I/O Module Features Chapter 2
Thermocouple Resolution
Thermocouple resolution indicates the degrees that an application temperature
must change before the 1756-IRT8I module connected to a thermocouple
module reports a change. Resolution depends on the following factors:
Thermocouple sensor type, any of the following:
Type B
Type C
Type D
Type E
Type J
Type K (default value)
Type N
Type R
Type S
Type T
Type TXK/XK (L)
Application temperature, that is, the temperature of the physical location
where the thermocouple is being used.
EXAMPLE
For example, when a 1756-IRT8I module is used with a thermocouple input
type in the following conditions, module resolution is 0.01 °:
Input channel is connected to a type K thermocouple
Application temperature is 400 °C (752 °F)
In other words, the application temperature must change by 0.01 ° or
greater for the 1756-IRT8I module used with a thermocouple input to
record a change. If the temperature stays in a range from
399.991…400.009 °C (751.984…752.016 °F), the module continues to
report an application temperature of 400 °C (752 °F).