Chapter 8 Calibrate the ControlLogix Isolated Analog I/O Modules
The Group High Reference Results dialog box indicates the status of each
channel. If the status is not OK for any channels, repeat the
calibration process.
If the error persists indefinitely, click Stop to exit calibration. The channel
remains calibrated to the accuracy level achieved at factory calibration.
15. Click Next.
The Calibration Completed dialog box indicates the status of each
channel.
16. Click Finish.