User Manual
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014 155
Calibrate the ControlLogix Isolated Analog I/O Modules Chapter 8
The Output Reference Signals dialog box appears, as shown below. It
indicates the channels are calibrated for a high reference and the
calibration range.
12. Click Next.
The Measure and Record Values dialog box appears.
13. For each channel being calibrated, use your current meter to measure the
reference value of each channel individually.
14. In the Recorded Reference (mA) column record the measured value for
each channel that was recorded and click Next.