Chapter 8 Calibrate the ControlLogix Isolated Analog I/O Modules
The Output Reference Signals dialog box appears. It indicates the channels
are calibrated for a low reference and the calibration range.
8. Click Next.
The Measure and Record Values dialog box appears.
9. For each channel being calibrated, use your current meter to measure the
reference value of each channel individually.
10. In the Recorded Reference (mA) column record the measured value for
each channel that was recorded and click Next.
The Group Low Reference Results dialog box indicates the status of each
channel. If the status is not OK for any channels, repeat the
calibration process.
11. Click Next.