User Manual

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014 145
Calibrate the ControlLogix Isolated Analog I/O Modules Chapter 8
3. On the Configuration tab, make sure the Input Type for each channel to
be calibrated is set to the same RTD input type.
The sensor type selection does not impact calibration.
4. On the Calibration tab, click Start Calibration.
5. When the warning appears, click OK.
6. Select the channels to be calibrated and click Next.