Owner manual

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011 91
Configure the Modules with RSLogix 5000 Software Chapter 7
General Tab
Complete the se instructions for a general configuration.
1. On the General tab, do these steps:
a. Type a name for the module.
b. Type an optional description for the module.
c. Select the slot number for the module.
2. On the Module Definition box, click Change.
The Module Definition dialog box appears.
3. Complete these actions:
Parameter Action Values
Series Displays the series letter that matches your
module’s series
N/A
Revision Choose the revision number that matches the label on the
side of your module, be sure that the minor revision
number also matches
N/A
Electronic Keying Choose the electronic keying method
See Electronic Keying on page 17
for more information
Exact Match
Compatible Module (default)
Disable Keying
Connection Choose the connection type Data - has more tabs on the Module Properties dialog box
than Listen-only because of configuration settings for
alarms, calibration
Listen-only - has no configuration data, does not send output
data (1756-OF8H module)
See Listen-only Mode on page 49 for more information.
Input Data Choose the input data mode Analog Only
Analog and HART PV
Analog and HART by Channel (available only for
firmware revision 2.1)
See HART Configuration
for more information.
Coordinated System Time Not configurable Timestamped
Data Format Not configurable Float