Appendix A Tag Definitions
BrokenWireFaults
(bit0…15)
INT Binary Indicates that current is not flowing through the module as expected. This might be caused by
broken wiring, RTB removal, or a powered-off field device.
ChxxBroken Wire BOOL Decimal BrokenWireFaults.0…BrokenWireFaults.15
HARTFaults
(Ch0…Ch15)
INT Binary Indicates a problem with HART data from the Field Device on Channel x.
Examples are HART not enabled, HART device not connected, HART communication failure due to
noise.
The following Field Device Status conditions also cause this to be set: Device Malfunction, PV Out
of Limits, Loop Current Saturated, and Loop Current Fixed.
ChxxHARTFault BOOL Decimal HARTFaults.0…HARTFaults.15
Ch00Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch00Fault for Overrange, Underrange, and/
or CalFault.
Ch00Overrange BOOL Ch00Status.05
Analog signal is greater than or equal to the maximum detectable signal. Because the signal
cannot be measured, it may be significantly above the maximum value.
Ch00Underrange BOOL Ch00Status.06
Analog signal is less than or equal to the minimum detectable signal. Because the signal cannot be
measured, it may be significantly below the minimum value.
Ch00CalFault BOOL Ch00Status.07
Set if an error occurs during calibration for Channel x, causing a bad calibration. Also sets CalFault.
Ch01Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch01Fault.
Ch02Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch02Fault.
Ch03Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch03Fault.
Ch04Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch04Fault.
Ch05Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch05Fault.
Ch06Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch06Fault.
Ch07Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch07Fault.
Ch08Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch08Fault.
Ch09Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch09Fault.
Ch10Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch10Fault.
Ch11Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch11Fault.
Ch12Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch12Fault.
Ch13Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch13Fault.
Ch14Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch14Fault.
Ch15Status SINT Binary Indicates various alarms on the analog signal. Also sets Ch15Fault.
Ch00Data REAL Float Value of analog signal on Channel 00 after conversion to engineering units.
Ch01Data REAL Float Value of analog signal on Channel 01 after conversion to engineering units.
Ch02Data REAL Float Value of analog signal on Channel 02 after conversion to engineering units.
Ch03Data REAL Float Value of analog signal on Channel 03 after conversion to engineering units.
Ch04Data REAL Float Value of analog signal on Channel 04 after conversion to engineering units.
Ch05Data REAL Float Value of analog signal on Channel 05 after conversion to engineering units.
Ch06Data REAL Float Value of analog signal on Channel 06 after conversion to engineering units.
Ch07Data REAL Float Value of analog signal on Channel 07 after conversion to engineering units.
Ch08Data REAL Float Value of analog signal on Channel 08 after conversion to engineering units.
Table 64 - Analog and HART PV (AB:1756_IF16H_HARTPV:I:0)