Module Troubleshooting Chapter 11
Additional Fault Codes - Channel Level
Each module has channel level error codes that are specific to the individual
modules. These channel level error codes, which display in the Module Fault box
on the Connection tab dialog box, are described in the following tables.
Table 52 - 1756-IF8H Channel Level Error Codes
Channel x Extended Status = Channel 0 Error Value + (x *16)
Channel Channel Status
01 23 4 5 6 7
Additional Fault Codes
16#0005 16#0015 16#0025 16#0035 16#0045 16#0055 16#0065 16#0075 Process Alarm Latch Set and
Disable All Alarms Set
16#0006 16#0016 16#0026 16#0036 16#0046 16#0056 16#0066 16#0076 Rate Alarm Latch Set and Alarm Disable Set
16#0007 16#0017 16#0027 16#0037 16#0047 16#0057 16#0067 16#0077 Invalid Input Range
16#0008 16#0018 16#0028 16#0038 16#0048 16#0058 16#0068 16#0078 Invalid Digital Filter
16#0009 16#0019 16#0029 16#0039 16#0049 16#0059 16#0069 16#0079 Invalid Rate Alarm
16#000A 16#001A 16#002A 16#003A 16#004A 16#005A 16#006A 16#007A High Signal and/or Low Signal outside of
selected input range
16#000B 16#001B 16#002B 16#003B 16#004B 16#005B 16#006B 16#007B High Signal Low Signal
16#000C 16#001C 16#002C 16#003C 16#004C 16#005C 16#006C 16#007C Sensor Offset set to NaN
16#000D 16#001D 16#002D 16#003D 16#004D 16#005D 16#006D 16#007D High Engineering = Low Engineering
16#000E 16#001E 16#002E 16#003E 16#004E 16#005E 16#006E 16#007E Invalid HART rate, HART rate fixed at 1:1
16#000F 16#001F 16#002F 16#003F 16#004F 16#005F 16#006F 16#007F High Alarm < Low Alarm
16#0010 16#0020 16#0030 16#0040 16#0050 16#0060 16#0070 16#0080 Low Low Alarm > Low
16#0011 16#0021 16#0031 16#0041 16#0051 16#0061 16#0071 16#0081 High High alarm < High Alarm
16#0012 16#0022 16#0032 16#0042 16#0052 16#0062 16#0072 16#0082 Invalid Alarm Deadband