Owner manual
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011 127
Getting HART Data By Using CIP MSG Chapter 8
56…91 Message HARTMsg CMD#12, Bytes 0…23
See HARTMsg on page 130
for more information.
92 PVCode SINT CMD#50, Bytes 0, 16#ff if not supported
93 SVCode CMD#50, Bytes 1, 16#ff if not supported
94 TVCode CMD#50, Bytes 2, 16#ff if not supported
95 FVCode CMD#50, Bytes 3, 16#ff if not supported
96 PVUnits CMD#3, Byte 4
97 SVUnits CMD#3, Byte 9, 0 if not present
98 TVUnits CMD#3, Byte 14, 0 if not present
99 FVUnits CMD#3, Byte 19, 0 if not present
100 TransferFunction CMD#15, Byte 1
101 RangeUnits CMD#15, Byte 2
102…103 Expanded Device
Type Code
CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 1…2 if HART revision is ≥ 7
104…107 PVLowerRange REAL CMD#15, Bytes 3…6
108…111 PVUpperRange CMD#15, Bytes 7…10
112…115 DampingValue CMD#15, Bytes 11…14
116 WriteProtectCode SINT CMD#15, Byte 15
117 Pad_8 for 32 bit
alignment
118…119 Private Label
Manufacturer 16 bit
CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 19…20 if HART revision is ≥ 7
Reply Size = 120 bytes
(1) See Appendix C on page 193
for related information.
Table 39 - Reply Packet - Request Succeeded
Offset Field Data Type Definition
(1)