Manual

5-4 Status Indicators and Troubleshooting
Publication 1756-UM524B-EN-P - December 2008
Table 5.D Firmware error codes
Error type Error
contents
Alpha-
numeric
display
NX46_
System
error
NX60_
System
error code
NX63_
status
level
NX64_
Status
code
NX61_
Send
error code
VX62_
Receive
error code
Event
log
source
User
action
Configu-
ration Error
Configuration
Error
ERR ON Error_
Code
N/A N/A N/A N/A NX SAM See
Table 5.E
System
Online
Error
NX DLINK is
inactive
ERR ON 0x11008000 E 0x11008000 N/A N/A NXDlink Major Fault
Data Buffer
Overflowed
RUN OFF N/A W 0x11008001 N/A N/A NXDlink Warning
Data Buffer
Upper Limit
RUN OFF N/A E 0x11008002 N/A N/A NXDlink Minor Fault
Data Buffer
Lower Limit
RUN OFF N/A I 0x11008003 N/A N/A NXDlink Informa-
tion
Receive Limit
Over
of Data Handle
RUN OFF N/A W 0x12008004 N/A N/A N/A Warning
MC Receive
Number
has missed
RUN OFF N/A I 0x11008004 N/A N/A NXDlink Informa-
tion
CPU Temp Over
Limit
RUN OFF N/A W 0x4e000001 N/A N/A NX SAM Warning
CPU Temp
Upper Limit
RUN OFF N/A E 0x4e000002 N/A N/A NX SAM Minor Fault
Send/
Receive
Error
CPU Temp
Lower Limit
RUN OFF N/A I 0x4e000003 N/A N/A NX SAM Informa-
tion
Send Error
Receive Error
RUN OFF N/A N/A N/A See Table 5.F NXDlink Individ-
ual error for
each handle.
See
Table 5.F.
Module
stopped
STOP OFF N/A N/A N/A N/A N/A N/A
Table 5.E Module error codes
No. Error code Decription User action
1 0x00000001 Incorrect Data Setting for
NX00_Node_Name_param
Correct the Data Setting for
NX00_Node_Name_param
2 0x00000002 Incorrect Data Setting for
NX01_IP_Address_Param
Correct the Data Setting for
NX01_IP_Address_Param
3 0x00000003 Incorrect Data Setting for
NX02_Subnet_Mask_Param
Correct the Data Setting for
NX02_Subnet_Mask_Param
4 0x00000004 Incorrect Data Setting for
NX03_Node_Param[0] “Logical
Node Number”
Correct the Data Setting for
NX03_Node_Param[0]
5 0x00000005 Incorrect Data Setting for
NX03_Node_Param[1] “Local Data
Field Number”
Correct the Data Setting for
NX03_Node_Param[1]