60 Rockwell Automation Publication 1756-UM022A-EN-P - November 2012
Chapter 5 Add, Configure, Monitor, and Replace CIP Safety I/O
IP address for EtherNet/IP networks
To set the IP address, you can adjust the rotary switches on the module, use
DHCP software, available from Rockwell Automation, or retrieve the
default address from nonvolatile memory.
Safety network number (SNN)
See page 61
for information on setting the SNN.
Configuration signature
See page 65
for information on when the configuration signature is set
automatically and when you need to set it.
Reaction time limit
See page 61
for information on setting the reaction time limit.
Safety input, output, and test parameters
You can configure CIP Safety I/O modules via the GuardLogix controller by
using the Logix Designer application.
Configure CIP Safety I/O
Modules
Add the CIP Safety I/O module to the communication module under the I/O
Configuration folder of the controller project.
1. Right-click the appropriate network and choose New Module.
2. Expand the Safety category and choose a CIP Safety I/O module.
3. Specify the module properties.
a. Modify the Module Definition settings, if required, by clicking
Change.
TIP
Safety I/O modules support standard and safety data. Module
configuration defines what data is available.
TIP
You cannot add or delete a CIP Safety I/O module while online.