Owner manual

56 Rockwell Automation Publication 1756-UM022A-EN-P - November 2012
Chapter 4 Communicate over Networks
These products are used with the DeviceNet networks and 1756-DNB module.
DeviceNet Connections for CIP Safety I/O Modules
To access CIP Safety devices on DeviceNet networks, add a 1756-DNB to the
I/O Configuration tree of the GuardLogix controller project.
CIP Safety I/O modules on DeviceNet networks are added to the project under
the 1756-DNB module, as described in Chapter
5, Add, Configure, Monitor,
and Replace CIP Safety I/O. When you add a CIP Safety I/O module, the Logix
Designer application automatically creates controller-scoped safety data tags for
that module.
Figure 15 - DeviceNet Module in Controller in the I/O Configuration Tree
Standard DeviceNet Connections
If you use standard DeviceNet I/O with your GuardLogix controller, you need to
allocate two connections for each 1756-DNB module. One connection is for
module status and configuration. The other connection is a rack-optimized
connection for the DeviceNet I/O data.
Table 17 - Product for Use with DeviceNet Networks
Product Is used to Required
Studio 5000 environment Configure ControlLogix projects.
Define DeviceNet communication.
Yes
RSNetWorx for DeviceNet software Configure DeviceNet devices.
Define the scan list for those devices.
Yes
RSLinx Classic or
RSLinx Enterprise software
Configure communication devices.
Provide diagnostics.
Establish communication between devices.
Yes