Owner manual

Rockwell Automation Publication 1756-UM022A-EN-P - November 2012 129
Status Indicators Appendix A
I/O Fault Codes
I/O faults indicated by the controller are indicated on the status display in one of
these formats:
I/O Fault Local:X #XXXX message
I/O Fault ModuleName #XXXX message
I/O Fault ModuleParent:X #XXXX message
The first part of the format is used to indicate the location of the faulted module.
How the location is indicated depends on your I/O configuration and the
module’s properties specified in the Logix Designer application.
Table 48 - Major Recoverable Fault Status Messages
Type Code Message Type Code Message
1 1 Run Mode Powerup 7 41 Bad Restore Type
1 60 Non-recoverable 7 42 Bad Restore Revision
1 61 Non-recoverable – Diagnostics Saved 7 43 Bad Restore Checksum
1 62 Non-recoverable – Program Saved 8 1 Keyswitch Change Ignored
3 16 I/O Connection Failure 11 1 Positive Overtravel Limit Exceeded
3 20 Chassis Failure 11 2 Negative Overtravel Limit Exceeded
3 21 11 3 Position Error Tolerance Exceeded
3 23 Connection Failure 11 4 Encoder Channel Connection Fault
4 16 Unknown Instruction 11 5 Encoder Noise Event Detected
4 20 Invalid Array Subscript 11 6 SERCOS Drive Fault
4 21 Control Structure LEN or POS < 0 11 7 Synchronous Connection Fault
4 31 Invalid JSR Parameter 11 8 Servo Module Fault
4 34 Timer Failure 11 9 Asynchronous Connection Fault
4 42 Invalid JMP Target 11 10 Motor Fault
4 82SFC Jump Back Failure 1111Motor Thermal Fault
4 83Value Out of Range 1112Drive Thermal Fault
4 84 Stack Overflow 11 13 SERCOS Communications Fault
4 89 Invalid Target Step 11 14 Inactive Drive Enable Input Detected
4 90 Invalid Instruction 11 15 Drive Phase Loss Detected
4 91Invalid Context 1116Drive Guard Fault
4 92 Invalid Action 11 32 Motion Task Overlap Fault
4 990
User-defined
11 33 CST Reference Loss Detected
4 991 18 1 CIP Motion Initialization Fault
4 992 18 2 CIP Motion Initialization Fault Mfg
4 993 18 3 CIP Motion Axis Fault
4 994 18 4 CIP Motion Axis Fault Mfg
4 995 18 5 CIP Motion Fault
4 996 18 6 CIP Module Fault
4 997 18 7 Motion Group Fault
4 998 18 8 CIP Motion Configuration Fault
4 999 18 9 CIP Motion APR Fault
6 1 Task Watchdog Expired 18 10 CIP Motion APR Fault Mfg
7 40 Save Failure 18 128 CIP Motion Guard Fault