User Manual
Rockwell Automation Publication 1756-UM005B-EN-P - January 2013 95
Calibrate the Module Chapter 6
If the measurement is within an acceptable range, the channel is marked
with an OK status, such as shown below. If the measurement is not within
an acceptable range, the software returns you to step 8
until the module
produces an acceptable output low reference level.
10. Repeat step 6
through step 9 to calibrate output channel 1 for 0…20 mA
operation.
When you have successfully calibrated both channels, the following
parameters appear.
This completes calibration of input and output channels.
Click Next to continue.
Click Finish to complete the calibration.