Calibrate the Module Chapter 6
6. Command the output channel to produce a low voltage reference level.
7. Record the voltage measurement shown on your voltage calibrator.
We recommend you use a minimum of four digits beyond the decimal
point.
The software commands the
output channel 0 to produce a low
voltage reference of 0.00V.
Click Next to proceed.
Click Next to proceed.