Calibrate the Module Chapter 6
To calibrate the high-speed analog module’s outputs, follow these steps.
1. Connect your current or voltage meter (depending on what mode your
channel is operating in) to the module. Remember, that you must wire the
module differently for Current mode than for Voltage mode. To see how to
wire for each mode, see page 63
.
2. Access the module’s properties page.
The Module Properties dialog box appears.
Choose Properties.
Right-click I/O Configuration
to see the menu.
Click the Output Configuration tab.