Module Features Chapter 3
The module may operate with values beyond the 4 mA…20 mA range. If an input
signal beyond the low and high signals is present at the module, such as 3 mA,
that data is represented in terms of the engineering units set during scaling.
Table 4
shows example values that may appear based the example mentioned
previously.
Features Specific to
Module Inputs
The following features are specific to high-speed analog I/O module inputs:
• Archiving
• Multiple Input Ranges
• Underrange/Overrange Detection
• Digital Filter
• Process Alarms
• Rate Alarm
• Synchronize Module Inputs
Table 4 - Current Values Represented in Engineering Units
Current Engineering Units Value
3 mA -6.25%
4 mA 0%
12 mA 50%
20 mA 100%
21 mA 106.25%